220kV Oil-immersed Power Transformer
REFERENCES
ISO 1461: Hot dip galvanized coatings on fabricated iron and steel articles – Specifications and test methods.
IEC 60076: Power transformers.
IEC 60044: Instrument transformers.
IEC 60296: Specification for unused mineral insulating oil for transformers and switchgear.
IEC 60354: Loading guide for oil – immersed power transformers.
IEC 60214: Tap-changers - Part 1: Performance requirements and test methods, Part 2: Application guide.
IEC 60512: Connectors for electronic equipment.
Performance
220kV Two-Winding Power Transformer With NVTC/OLTC | ||||||
Rated Capacity (kVA) | Rated Voltage (kV) | Vector Group | Losses (W) | Impedance Voltage (%) | ||
HV | LV | No load | On load | |||
31500 | 220 ±2×2.5% | 6.3 | YNd11 | 29000 | 135000 | 12-14 |
40000 | 6.6 | 35000 | 158000 | |||
50000 | 10.5 | 41000 | 189000 | |||
63000 | 11 | 49000 | 221000 | |||
90000 | 10.5 | 65000 | 288000 | |||
120000 | 13.8 11 | 80000 | 347000 | |||
150000 | 11 | 96000 | 405000 | |||
180000 | 13.8 | 109000 | 459000 | |||
240000 | 15.75 | 136000 | 567000 | |||
300000 | 15.75 | 160000 | 675000 | |||
360000 | 18 | 184000 | 774000 |
220kV Three-Winding Power Transformer With NVTC/OLTC | |||||||||
Rated Capacity (kVA) | Rated Voltage (kV) | Vector Group | Losses (W) | Impedance Voltage (%) | Capacity Arrange (%) | ||||
HV | MV | LV | No load | On load | Step Up | Step Down | |||
31500 | 220 ±2×2.5% | 69 121 | 6.3 6.6 | YNyn0d11 | 34000 | 162000 | HV-MV 22-24 HV-LV 12-14 MV-LV 7-9 | HV-MV 12-14 HV-LV 22-24 MV-LV 7-9 | 100/100/100 100/50/100 100/100/50 |
40000 | 10.5 11 | 40000 | 189000 | ||||||
50000 | 35 | 48000 | 225000 | ||||||
63000 | 38.5 | 56000 | 261000 | ||||||
90000 | 10.5 11 13.8 | 73000 | 351000 | ||||||
120000 | 35 38.5 | 90000 | 432000 | ||||||
150000 | 11 13.8 | 106000 | 513000 | ||||||
180000 | 15.75 35 | 121000 | 585000 | ||||||
240000 | 38.5 | 149000 | 720000 |
INSULATION LEVELS
Nominal system voltage (kV, rms) | Highest system voltage (kV, rms) | Lightning Impulse withstand voltage, dry (kV, peak) | Power frequency withstand voltage, wet (kV, rms) |
33 | 36 | 200 | 95 |
132 | 145 | 650/750 (internal/external) | 275/325 (internal/external) |
AUXILIARY SUPPLIES
Equipment generally rated for the following auxiliary power supplies:
(a) Cooler control circuits: 220V, 240 V, single phase, 50Hz
(b) Tap changer control: 220V, 240 V, single phase, 50Hz
(c) Cooling fan motors: 380V, 415 V, three phase, 50Hz
(d) Tap changer motor: 380V, 415 V, three phase, 50Hz
ROUTINE TEST to IEC 60076 (to be done during acceptance testing at factory)
• Measurement of winding resistance
• Ratio test
• Vector group
• Separate source voltage withstand test
• Induced over-voltage
• Insulation resistance
• Oil leakage test on fully assembled transformer for 12 hours
• Measurement of impedance voltage
• Magnetic balance
• Measurement of no-load loss and current
• Measurement of load loss (at normal & extreme taps)
• Tests on on-load tap-changer
• Tests on on-load tap-changer remote control panel
• Efficiency at 50%, 75%, 100% loading at unity p.f and rated terminal voltage (Corrected to 75C)
• Lightning impulse withstand test
Type Tests to IEC 60076 (to be done during acceptance testing at factory)
• Temperature rise test – To be performed on one unit during acceptance testing.
Lightning Impulse Withstand Test is already listed under Routine Tests as per IEC 60076.
Test Facility
Installation
220kV Oil-immersed Power Transformer