66 110 220kV Oil-immersed Power Transformer

66 110 220kV Oil-immersed Power Transformer
Product Detailed
Related Categories:Transformers
Economic or deluxe solution optional Better cost performance IEC Standards Criteria New factory for better price NVTC/ OLTC

REFERENCES

ISO 1461: Hot dip galvanized coatings on fabricated iron and steel articles – Specifications and test methods.

IEC 60076: Power transformers.

IEC 60044: Instrument transformers.

IEC 60296: Specification for unused mineral insulating oil for transformers and switchgear.

IEC 60354: Loading guide for oil – immersed power transformers.

IEC 60214: Tap-changers - Part 1: Performance requirements and test methods, Part 2: Application guide.

IEC 60512: Connectors for electronic equipment.

Performance

66kV Two-Winding Power Transformer With NVTC/OLTC
Rated Capacity (kVA)Rated Voltage (kV)Vector GroupLosses (W)

Impedance Voltage

(%)

HVTapping RangeLVNo loadOn load
63063 66 69±5%6.3 6.6 10.5 11Yd11136075608.0
80016208830
1000192010440
1250226012340
1600272014850
2000320017550
2500376020700
3150YNd11448024300
4000528028800
5000624032400
6300±2×2.5%8000360009.0
8000960042750
100001136050400
125001336059850
160001608073530
200001904089100
2500022480105300
3150026720126900
4000032000148950
5000037760184500
6300044880222300

 

 

 

 

 

 

 

110kV Two-Winding Power Transformer With NVTC/OLTC

Rated

Capacity

 (kVA)

Rated Voltage (kV)

Vector

 Group

Losses (W)

Impedance

 Voltage

 (%)

HV

Tapping

 Range

LVNo loadOn load
6300110 121±2×2.5%6.3 6.6 10.5 11YNd1180003690010.5
8000960045000
100001120053100
125001320063000
160001600077400
200001900093600
2500022400110700
3150026700133200
4000031800156600
5000037600194400
6300044600234000
110kV Three-Winding Power Transformer With   NVTC/OLTC

Rated

Capacity

 (kVA)

Rated Voltage (kV)

Vector

 Group

Losses (W)Impedance Voltage (%)
HV

Tapping

 Range

LVNo loadOn loadStep UpStep Down
6300

110 ±2×2.5%  

121 ±2×2.5%

35 38.5 ±2×2.5%6.3 6.6 10.5 11YNyn0d11960047700

HV-MV 17-18

HV-LV 10.5

MV-LV 6.5

HV-MV 10.5

HV-LV 17-18 MV-LV 6.5

80001150056700
100001360066600
125001600078300
160001930095400
2000022800112500
2500027000133200
3150032000157500
4000038200189000
5000045200225000
6300053600270000
220kV Two-Winding Power Transformer With NVTC/OLTC

Rated

 Capacity

 (kVA)

Rated Voltage

 (kV)

Vector

Group

Losses (W)

Impedance

 Voltage

 (%)

HVLVNo loadOn load
31500220 ±2×2.5% 6.3YNd112900013500012-14
400006.635000158000
5000010.541000189000
630001149000221000
9000010.565000288000
12000013.8 1180000347000
1500001196000405000
18000013.8109000459000
24000015.75136000567000
30000015.75160000675000
36000018184000774000
220kV Three-Winding Power Transformer With   NVTC/OLTC

Rated

Capacity

 (kVA)

Rated Voltage

 (kV)

Vector

 Group

Losses (W)

Impedance

 Voltage (%)

Capacity

Arrange

(%)

HVMVLVNo loadOn loadStep UpStep Down
31500

220

±2×2.5% 

69

121

6.3

 6.6

YNyn0d1134000162000

HV-MV 22-24

HV-LV 12-14

MV-LV 7-9

HV-MV 12-14

HV-LV

 22-24

MV-LV

7-9

100/100/100

100/50/100

100/100/50

40000

10.5

 11

40000189000
500003548000225000
6300038.556000261000
90000

10.5

 11

13.8

73000351000
120000

35

38.5

90000432000
150000

11  

 13.8

106000513000
180000

15.75 

  35

121000585000
24000038.5149000720000

 

 ROUTINE TEST to IEC 60076 (to be done during acceptance testing at factory)

 

• Measurement of winding resistance

• Ratio test

• Vector group

• Separate source voltage withstand test

• Induced over-voltage

• Insulation resistance

• Oil leakage test on fully assembled transformer for 12 hours

• Measurement of impedance voltage

• Magnetic balance

• Measurement of no-load loss and current

• Measurement of load loss (at normal & extreme taps)

• Tests on on-load tap-changer

• Tests on on-load tap-changer remote control panel

• Efficiency at 50%, 75%, 100% loading at unity p.f and rated terminal voltage (Corrected to 75C)

• Lightning impulse withstand test

Type Tests to IEC 60076 (to be done during acceptance testing at factory)

• Temperature rise test – To be performed on one unit during acceptance testing.

Lightning Impulse Withstand Test is already listed under Routine Tests as per IEC 60076.

 Test Facility

66 110 220kV Oil-immersed Power Transformer